CVE-2017-6866 1 Siemens 1 Xhq Server 2025-04-20 N/A
A vulnerability was discovered in Siemens XHQ server 4 and 5 (4 before V4.7.1.3 and 5 before V5.0.0.2) that could allow an authenticated low-privileged remote user to gain read access to data in the XHQ solution exceeding his configured permission level.
CVE-2017-2688 1 Siemens 1 Ruggedcom Rox I 2025-04-20 N/A
The integrated web server in Siemens RUGGEDCOM ROX I (all versions) at port 10000/TCP could allow remote attackers to perform actions with the privileges of an authenticated user, provided the targeted user has an active session and is induced into clicking on a malicious link or into visiting a malicious website, aka CSRF.
CVE-2017-9945 1 Siemens 2 7km Pac Switched Ethernet Profinet Expansion Module, 7km Pac Switched Ethernet Profinet Expansion Module Firmware 2025-04-20 N/A
In the Siemens 7KM PAC Switched Ethernet PROFINET expansion module (All versions < V2.1.3), a Denial-of-Service condition could be induced by a specially crafted PROFINET DCP packet sent as a local Ethernet (Layer 2) broadcast. The affected component requires a manual restart via the main device to recover.
CVE-2017-9946 1 Siemens 8 Apogee Pxc, Apogee Pxc Firmware, Apogee Pxc Modular and 5 more 2025-04-20 7.5 High
A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions <V3.5. An attacker with network access to the integrated web server (80/tcp and 443/tcp) could bypass the authentication and download sensitive information from the device.
CVE-2017-2681 1 Siemens 155 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200 Pn Io and 152 more 2025-04-20 6.5 Medium
Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected.
CVE-2017-9947 1 Siemens 8 Apogee Pxc, Apogee Pxc Firmware, Apogee Pxc Modular and 5 more 2025-04-20 5.3 Medium
A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions <V3.5. A directory traversal vulnerability could allow a remote attacker with network access to the integrated web server (80/tcp and 443/tcp) to obtain information on the structure of the file system of the affected devices.
CVE-2017-6458 4 Apple, Hpe, Ntp and 1 more 5 Mac Os X, Hpux-ntp, Ntp and 2 more 2025-04-20 8.8 High
Multiple buffer overflows in the ctl_put* functions in NTP before 4.2.8p10 and 4.3.x before 4.3.94 allow remote authenticated users to have unspecified impact via a long variable.
CVE-2017-6865 1 Siemens 16 Pcs 7, Primary Setup Tool, Security Configuration Tool and 13 more 2025-04-20 N/A
A vulnerability has been identified in Primary Setup Tool (PST) (All versions < V4.2 HF1), SIMATIC Automation Tool (All versions < V3.0), SIMATIC NET PC-Software (All versions < V14 SP1), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC STEP 7 (TIA Portal) V13 (All versions < V13 SP2), SIMATIC STEP 7 (TIA Portal) V14 (All versions < V14 SP1), SIMATIC STEP 7 V5.X (All versions < V5.6), SIMATIC WinAC RTX 2010 SP2 (All versions), SIMATIC WinAC RTX F 2010 SP2 (All versions), SIMATIC WinCC (TIA Portal) V13 (All versions < V13 SP2), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1), SIMATIC WinCC V7.2 and prior (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Update 15), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd1), SIMATIC WinCC flexible 2008 (All versions < flexible 2008 SP5), SINAUT ST7CC (All versions installed in conjunction with SIMATIC WinCC < V7.3 Update 15), SINEMA Server (All versions < V14), SINUMERIK 808D Programming Tool (All versions < V4.7 SP4 HF2), SMART PC Access (All versions < V2.3), STEP 7 - Micro/WIN SMART (All versions < V2.3), Security Configuration Tool (SCT) (All versions < V5.0). Specially crafted PROFINET DCP broadcast packets sent to the affected products on a local Ethernet segment (Layer 2) could cause a Denial-of-Service condition of some services. The services require manual restart to recover.
CVE-2017-6867 1 Siemens 3 Simatic Wincc, Simatic Wincc \(tia Portal\), Simatic Wincc Runtime 2025-04-20 N/A
A vulnerability was discovered in Siemens SIMATIC WinCC (V7.3 before Upd 11 and V7.4 before SP1), SIMATIC WinCC Runtime Professional (V13 before SP2 and V14 before SP1), SIMATIC WinCC (TIA Portal) Professional (V13 before SP2 and V14 before SP1) that could allow an authenticated, remote attacker who is member of the "administrators" group to crash services by sending specially crafted messages to the DCOM interface.
CVE-2017-6871 1 Siemens 2 Simatic Wincc Sm\@rtclient, Simatic Wincc Sm\@rtclient Lite 2025-04-20 N/A
A vulnerability was discovered in Siemens SIMATIC WinCC Sm@rtClient for Android (All versions before V1.0.2.2) and SIMATIC WinCC Sm@rtClient for Android Lite (All versions before V1.0.2.2). An attacker with physical access to an unlocked mobile device, that has the affected app running, could bypass the app's authentication mechanism under certain conditions.
CVE-2016-8566 1 Siemens 1 Sicam Pas\/pqs 2025-04-20 7.8 High
An issue was discovered in Siemens SICAM PAS before 8.00. Because of Storing Passwords in a Recoverable Format, an authenticated local attacker with certain privileges could possibly reconstruct the passwords of users for accessing the database.
CVE-2017-9941 1 Siemens 1 Sipass Integrated 2025-04-20 N/A
A vulnerability was discovered in Siemens SiPass integrated (All versions before V2.70) that could allow an attacker in a Man-in-the-Middle position between the SiPass integrated server and SiPass integrated clients to read or modify the network communication.
CVE-2017-9942 1 Siemens 1 Sipass Integrated 2025-04-20 N/A
A vulnerability was discovered in Siemens SiPass integrated (All versions before V2.70) that could allow an attacker with local access to the SiPass integrated server or SiPass integrated client to potentially obtain credentials from the systems.
CVE-2016-7987 1 Siemens 8 Eta2 Firmware, Eta4 Firmware, Sicam Ak and 5 more 2025-04-20 N/A
An issue was discovered in Siemens ETA4 firmware (all versions prior to Revision 08) of the SM-2558 extension module for: SICAM AK, SICAM TM 1703, SICAM BC 1703, and SICAM AK 3. Specially crafted packets sent to Port 2404/TCP could cause the affected device to go into defect mode. A cold start might be required to recover the system, a Denial-of-Service Vulnerability.
CVE-2017-9944 1 Siemens 2 7kt Pac1200 Data Manager, 7kt Pac1200 Data Manager Firmware 2025-04-20 N/A
A vulnerability has been identified in Siemens 7KT PAC1200 data manager (7KT1260) in all versions < V2.03. The integrated web server (port 80/tcp) of the affected devices could allow an unauthenticated remote attacker to perform administrative operations over the network.
CVE-2017-6864 1 Siemens 1 Ruggedcom Rox I 2025-04-20 N/A
The integrated web server in Siemens RUGGEDCOM ROX I (all versions) at port 10000/TCP could allow an authenticated user to perform stored Cross-Site Scripting attacks.
CVE-2017-5711 3 Asus, Intel, Siemens 394 B150-a, B150-a Firmware, B150-plus and 391 more 2025-04-20 7.8 High
Multiple buffer overflows in Active Management Technology (AMT) in Intel Manageability Engine Firmware 8.x/9.x/10.x/11.0/11.5/11.6/11.7/11.10/11.20 allow attacker with local access to the system to execute arbitrary code with AMT execution privilege.
CVE-2016-8567 1 Siemens 1 Sicam Pas\/pqs 2025-04-20 9.8 Critical
An issue was discovered in Siemens SICAM PAS before 8.00. A factory account with hard-coded passwords is present in the SICAM PAS installations. Attackers might gain privileged access to the database over Port 2638/TCP.
CVE-2017-12734 1 Siemens 2 Logo\!8 Bm Fs-05, Logo\!8 Bm Fs-05 Firmware 2025-04-20 7.5 High
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V1.81.2). An attacker with network access to the integrated web server on port 80/tcp could obtain the session ID of an active user session. A user must be logged in to the web interface. Siemens recommends to use the integrated webserver on port 80/tcp only in trusted networks.
CVE-2017-9938 1 Siemens 1 Simatic Logon 2025-04-20 N/A
A vulnerability was discovered in Siemens SIMATIC Logon (All versions before V1.6) that could allow specially crafted packets sent to the SIMATIC Logon Remote Access service on port 16389/tcp to cause a Denial-of-Service condition. The service restarts automatically.